How does a bypass soft starter achieve smooth motor starting and avoid grid surges?

Publish Time: 2025-08-27
In industrial production, high-power AC motors generated by direct starting generate instantaneous surge currents as high as 5–8 times the rated current. This not only causes severe fluctuations in the power grid but can also trigger voltage sags, distribution system trips, and even disrupt the normal operation of other equipment on the same grid. Furthermore, the immense mechanical impact accelerates wear on transmission components such as the motor, couplings, and gearboxes, reducing equipment life. To address this challenge, bypass soft starters have emerged. Using advanced power electronics and intelligent control strategies, they achieve "soft starting" of motors, effectively suppressing starting currents and protecting the power grid and equipment. They have become a core device for modern industrial motor control.

1. Thyristor Voltage Regulation Technology: Achieving Smooth Voltage Rising

The core of a bypass soft starter lies in its use of anti-parallel thyristor (SCR) modules connected in series in the motor's stator circuit. During startup, the control system gradually increases the voltage applied to the motor by adjusting the conduction angle of the thyristors. Initially, the voltage slowly increases from 30%–50% of the rated voltage, enabling the motor to start with low torque. As the speed increases, the voltage steadily rises to full voltage according to a pre-set ramp curve. This process transforms the previously hard start (instant full voltage access) into a soft start (gradual voltage increase), limiting the starting current to 2.5–4 times the rated current, significantly reducing the impact on the power grid.

2. Controllable Starting Process, Reducing Mechanical Stress

Because voltage and torque are proportional to the square, soft starters produce less torque during low-voltage starting, avoiding the mechanical shock caused by a sudden "rush" of the motor. This is particularly important for starting equipment under load, such as pumps, fans, and compressors. It effectively prevents water hammer, belt slippage, and gear damage, extending the life of the transmission system.

3. Bypass Contactor: Automatically switches after starting to reduce losses.

The "bypass" function is a key design feature of this type of soft starter. Once the motor has started and reached rated speed, the bypass contactor (or external contactor) within the soft starter automatically closes, shorting the thyristor module from the main circuit and allowing the motor to operate directly from the three-phase power supply. At this point, the main current no longer flows through the thyristors, but instead is conducted through the low-impedance contactor. This avoids power loss and heat generation in the thyristors during long-term operation, improving system efficiency and reliability.

4. Reduces Grid Voltage Fluctuations and Ensures System Stability

High current surges can cause instantaneous grid voltage drops, impacting the normal operation of sensitive equipment such as PLCs, sensors, and lighting. Bypass soft starters significantly mitigate this "voltage sag" phenomenon by limiting the starting current, ensuring stable operation of factory power distribution systems. They are particularly suitable for industrial scenarios with limited grid capacity or dense loads.

5. Integrated Protection Functions Enhance System Safety

Bypass soft starters typically have multiple built-in protection features, including overcurrent, overload, phase loss, stall, and overheating. If an abnormality is detected, the output is immediately stopped and an alarm is issued to prevent motor burnout or escalation of the accident. It also supports remote start and stop, status feedback, and fault logging, facilitating integration into DCS or SCADA systems for intelligent management.

The bypass soft starter utilizes a dual mechanism: thyristor voltage regulation to control the starting process, and a bypass contactor to implement operational switching. This ensures smooth motor starting and grid surge suppression. It not only protects the motor and mechanical system but also improves the stability and energy efficiency of the entire power supply network.
×